Accident of power supply system due to corrosion of metallic materials in substation induced by industrial atmospheric emissions has become an important problem, which affects the network security. Among others, the corrosion of copper T2 was the most serious. In this paper, with a homemade setup as indoor accelerated corrosion test means, the corrosion behavior of copper in cyclic drywet environment with gas mixture of SO2 and H2S was investigated by means of electrochemical measurement and microscopic characterization. While a BP neural netwo...