A Multifunctional Arc Suppression Device Based on Hybrid Grid-Connected Converters

认领
导出
Link by DOI
反馈
分享
QQ微信 微博
成果类型:
期刊论文
作者:
Huang, Zejun;Guo, Qi;Tu, Chunming;Sun, Kai;Wang, Lei;...
通讯作者:
Guo, Q
作者机构:
[Tu, Chunming; Huang, Zejun; Guo, Qi; Wang, Lei; Hou, Yuchao] Hunan Univ, Coll Elect & Informat Engn, Changsha 410082, Peoples R China.
[Sun, Kai] Tsinghua Univ, Dept Elect Engn, Beijing 100084, Peoples R China.
[Jiang, Fei] Changsha Univ Sci & Technol, Sch Elect & Informat Engn, Changsha 410004, Peoples R China.
通讯机构:
[Guo, Q ] H
Hunan Univ, Coll Elect & Informat Engn, Changsha 410082, Peoples R China.
语种:
英文
关键词:
Reactive power;Legged locomotion;Inductance;Costs;Topology;Capacitors;Regulation;Voltage control;Switches;Power grids;Arc suppression;grid connected converter;reactive power compensation;single line-to-ground (SLG) fault
期刊:
IEEE Transactions on Industrial Electronics
ISSN:
0278-0046
年:
2025
页码:
1-10
基金类别:
National Natural Science Foundation of China [52077072]; China Postdoctoral Science Foundation [2023T160207]
机构署名:
本校为其他机构
院系归属:
电气与信息工程学院
摘要:
Since the voltage amplitude of the arc suppression device is different during the normal operation and single line-to-ground fault, the problems of high cost and low module utilization rate are serious. An integrated grid-connected converter (IGCC) with reactive power compensation and fault regulation ability is proposed. First, the topology and operation mechanism of IGCC are introduced in this article. A common unit combining neutral point clamped (NPC) and cascaded H-bridge is formed by improving the traditional arc suppression device. By adding a fourth leg in the NPC module and connecting...