[Zhang, Li; Su, Wei; Qian, Yihua; Chen, Tiansheng; Fan, Shengping; Fu, Qiang; Zhao, Yaohong] Guangdong Power Grid Co Ltd, Elect Power Res Inst, Guangzhou 510080, Guangdong, Peoples R China
[Zhu, Zhiping; Wang, Deng] Changsha Univ Sci & Technol, Sch Chem & Biol Engn, Changsha 410114, Hunan, Peoples R China
通讯机构:
[Zhang, Li] G
Guangdong Power Grid Co Ltd, Elect Power Res Inst, Guangzhou 510080, Guangdong, Peoples R China.
Research Project of China Southern Power Grid Co., Ltd. [GDKJQQ20152036]; National Natural Science Foundation of ChinaNational Natural Science Foundation of China (NSFC) [21541003]
机构署名:
本校为其他机构
院系归属:
化学与生物工程学院
摘要:
Recently, a kind of 110-kV transformer resistance decline defect was found during our routine preventive test of transformers in the Guangdong power grid. The number of defective transformers reached thirty. This phenomenon seriously threatened the safe and steady operation of the power grid. The analysis and treatment of this resistance decline defect were carried out. The key reason for this defect was confirmed. The insulating characteristics of insulating oil decreased. Aminopyrine is a kind of medicine used as an antipyretic analgesic. However, it was seldom investigated by the electric p...